Cala error codes

Updated November 11, 2026

Type the code on your Cala's screen to see what it means and what to do. Your Cala protects itself and retries on its own, so many codes clear without you doing anything.

When something needs attention, your Cala shows a short code on its Home screen in front of a message, like L_24_16: Floor Leak Detected.

Read a code

The first letter tells you which part of your Cala the code is about:

Letter About Shown on the Home screen
HHeat pumpYes
SSensorsYes
EHeating elementsYes
LLeaksYes
CWi-FiNo
OSoftware updatesNo
GClockNo

If there is more than one problem at once, the Home screen shows the codes followed by Multiple errors occurred. Look up each code.

What to do first

  1. Write down the code and the message on the Home screen.

  2. If the leak alarm is sounding, follow Leak and heat pump alarms now.

  3. Type the code in Find your code above and follow What to do.

  4. If the code stays or keeps coming back, contact your installer or [email protected] with the code.

Heat pump codes (H)

Most heat pump codes mean the heat pump paused to protect itself. Your Cala waits, then tries again on its own. The wait starts at 1 minute and gets longer each time the same problem comes back. For most of these codes the electric heating elements take over while the heat pump waits, so you still have hot water.

A heat pump code stays on the Home screen until the heat pump next starts normally, so it can describe something that has already passed.

Code and message What it means What to do For your Cala Pro

H_0_0
Upper Tank is Over Temperature

H_1_0
Lower Tank is Over Temperature

H_2_0
Top Tank is Over Temperature

H_3_0
Delivery Tank is Over Temperature

The water at one of the tank's temperature sensors (upper, lower, top or the hot outlet) is hotter than the tank's maximum temperature limit. Your Cala stops heating until the water cools, then carries on by itself. Nothing to do if the code goes away. If it stays or keeps coming back, contact your installer or [email protected]. Check the maximum temperature knob on the unit against the customer's setpoint. Check that the named thermistor is fully seated and reads a sensible temperature. Contact Cala support if the tank really is over the limit.

H_0_4
Upper Tank Dry Fire Protection Triggered

H_1_4
Lower Tank Dry Fire Protection Triggered

H_2_4
Top Tank Dry Fire Protection Triggered

During its start-up checks (the first time it is powered, or after more than 24 hours without power), your Cala found that the tank may not be full of water. It does not heat until the check passes, which protects the heating elements. Make sure the cold water shut-off valve to your water heater is open. Open a hot tap until the water runs steadily with no sputtering, then close it. If the code is still there, contact your installer or [email protected]. Fill the tank completely and bleed the air at a hot tap. Then select RERUN on the diagnostics screen. Check that the tank thermistors are seated in their wells.

H_13_5
Compressor Overcurrent Detected

Your Cala measured more electrical current than expected while the heat pump was running. It pauses heating, waits and tries again. Wait for your Cala to try again. If the code keeps coming back, contact your installer or [email protected]. Measure supply voltage and current at the unit. Inspect the compressor and inverter wiring. Contact Cala support before replacing parts.

H_13_6
Compressor Undervoltage Detected

Not used by current Cala software. You should not see this code. If you do, contact [email protected]. Contact Cala support.

H_13_7
Compressor Overvoltage Detected

H_13_28
Compressor Reported Overvoltage

H_13_27
Compressor Reported Undervoltage

The voltage reaching the heat pump is higher or lower than it can run on. The heat pump waits and tries again. The heating elements keep your water hot in the meantime. This often passes on its own, for example after a power outage. If lights dim or flicker in your home, call your electric utility or an electrician. If the code keeps coming back, contact your installer or [email protected]. Measure the supply voltage at the unit's terminal block, at rest and with the unit heating. Check the breaker and supply wiring connections.

H_13_9
Compressor Restart Frequency Too High

The heat pump has started 6 times in the past hour, the most your Cala allows. It waits before the next start. The heating elements still work. Nothing to do. It clears within the hour. If you see it often, contact your installer or [email protected]. Look for another code that is stopping the heat pump shortly after each start.

H_13_15
Heat Pump timed out waiting for a response

H_13_17
Heat Pump communication reported timed out

H_13_10
Compressor Stopped Unexpectedly

Your Cala's controller and the heat pump's drive stopped talking to each other, or the heat pump stopped when it wasn't asked to. The heat pump can't run until the connection is back. The heating elements still work. Restart your Cala once. If the code comes back, contact your installer or [email protected]. With power off at the breaker, check that the communication and power cables between the main board and the compressor inverter are fully seated and undamaged.

H_13_13
Heat Pump reported a failure to start

H_13_11
Compressor Reported Overcurrent

The heat pump's drive reported that the compressor did not start, or drew too much current. The heat pump waits and tries again. The heating elements keep your water hot in the meantime. Wait for your Cala to try again. If the code keeps coming back, contact your installer or [email protected]. Check supply voltage and the compressor and inverter connections. Contact Cala support before replacing parts.

H_26_0
Intelligent Power Module report overtemp

The electronics that drive the heat pump got too hot. The heat pump waits and tries again. The heating elements keep your water hot in the meantime. Clean the air filter. Make sure nothing blocks the air going into or out of your Cala and that the room isn't very hot. If the code keeps coming back, contact your installer or [email protected]. Check that the fan runs and that airflow and any ducting are clear. Check the room temperature.

H_14_0
Heat Pump Pressure Difference Too High

H_9_0
Heat Pump Discharge Pressure Too High

The pressure inside the heat pump is higher than expected. If it stays high, the heat pump waits and tries again. The heating elements keep your water hot in the meantime. Clean the air filter and make sure nothing blocks the air going into or out of your Cala. If the code keeps coming back, contact your installer or [email protected]. Check the fan, airflow and the pressure sensor connectors. Never open the sealed refrigerant circuit. Contact Cala support.

H_6_1
Heat Pump Suction Temperature Too Low

H_10_1
Heat Pump Suction Pressure Too Low

The cold side of the heat pump got colder than it should. This is normal after a very large amount of hot water has been used and the tank is full of cold water, or when the air around your Cala is very cold. Your Cala recovers by itself, using the heating elements if it needs to. Give the tank several hours to recover. Clean the air filter. If it happens without heavy hot water use, or the tank hasn't recovered after 12 hours, contact your installer or [email protected]. Check the air filter, fan and airflow. Check the room temperature: the heat pump runs between 37 °F and 120 °F. A space that stays cold may need ducting or a warmer location. Check the suction sensor connectors. Never open the sealed refrigerant circuit.

H_4_0
Heat Pump Discharge Temperature Too High

H_6_0
Heat Pump Suction Temperature Too High

The heat pump is running hotter than expected. It waits and tries again. The heating elements keep your water hot in the meantime. Clean the air filter. Make sure nothing blocks the air going into or out of your Cala and that the room isn't very hot. If the code keeps coming back, contact your installer or [email protected]. Check the fan and airflow. Check that the discharge and suction line thermistors are attached to their pipes. Never open the sealed refrigerant circuit. Contact Cala support.

H_4_1
Heat Pump Discharge Temperature Too Low

The heat pump ran for an hour without warming up the way it should. It waits and tries again. The heating elements keep your water hot in the meantime. If the code keeps coming back, contact your installer or [email protected]. Check that the discharge line thermistor is attached to its pipe and connected. Never open the sealed refrigerant circuit. Contact Cala support.

H_5_1
Liquid Line temp is low relative to compressor start

H_10_0
Heat Pump Suction Pressure Too High

H_9_1
Heat Pump Discharge Pressure Too Low

Used only when Cala tests each water heater at the factory. You should not see these codes at home. If you do, contact [email protected]. Contact Cala support.

Sensor codes (S)

Your Cala checks its sensors all the time. If a reading is outside the range that makes sense for more than 5 seconds, it pauses heating until the reading is back, then carries on by itself.

Each sensor has up to three codes. The last number tells you what is wrong with the reading: 0 means Over Range (too high), 1 means Under Range (too low) and 2 means NaN (no reading at all).

Code and message What it means What to do For your Cala Pro

S_0_0, S_0_1, S_0_2
Upper Thermistor is Over Range / Under Range / NaN

S_1_0, S_1_1, S_1_2
Lower Thermistor is Over Range / Under Range / NaN

S_2_0, S_2_1, S_2_2
Top Thermistor is Over Range / Under Range / NaN

S_3_0, S_3_1, S_3_2
Delivery Thermistor is Over Range / Under Range / NaN

One of the water temperature sensors (thermistors) in the tank or at the hot outlet is giving a reading that can't be right. Your Cala pauses heating until the reading returns. Restart your Cala once. If the code stays or comes back, contact your installer or [email protected]. With power off at the breaker, check the named thermistor's connector at the main board and its cable. Under Range usually means an open or unplugged circuit; Over Range usually means a short. Measure the thermistor and replace it if it is out of spec.

S_4_0, S_4_1, S_4_2
Discharge Line Thermistor is Over Range / Under Range / NaN

S_5_0, S_5_1, S_5_2
Liquid Line Thermistor is Over Range / Under Range / NaN

S_6_0, S_6_1, S_6_2
Suction Line Thermistor is Over Range / Under Range / NaN

One of the temperature sensors on the heat pump's pipes is giving a reading that can't be right. Your Cala pauses heating until the reading returns. Restart your Cala once. If the code stays or comes back, contact your installer or [email protected]. With power off at the breaker, check the named thermistor's connector and cable, and that the thermistor is attached to its pipe. Under Range usually means an open or unplugged circuit; Over Range usually means a short.

S_7_0
Ambient Temperature is Over Range

S_7_1
Ambient Temperature is Under Range

The air around your Cala is hotter than 120 °F or colder than 37 °F, outside the range the heat pump runs in. The heat pump rests for 24 hours and the heating elements keep your water hot. Nothing to do: you still have hot water. Once the room is back to a normal temperature, you can restart your Cala to bring the heat pump back sooner. If the space is often that hot or cold, talk to your installer. Confirm the room temperature at the unit. A space that is regularly outside 37 °F to 120 °F may need ducting or a different location.

S_7_2
Ambient Temperature is NaN

S_8_0, S_8_1, S_8_2
Ambient Humidity is Over Range / Under Range / NaN

The sensor that measures the air temperature and humidity around your Cala isn't giving a usable reading. Your Cala pauses heating until the reading returns. Restart your Cala once. If the code stays or comes back, contact your installer or [email protected]. With power off at the breaker, check the air temperature and humidity sensor's cable and connector. Replace the sensor if the fault stays.

S_9_0, S_9_1, S_9_2
Delivery Pressure is Over Range / Under Range / NaN

S_10_0, S_10_1, S_10_2
Suction Pressure is Over Range / Under Range / NaN

One of the pressure sensors inside the heat pump is giving a reading that can't be right. These measure the heat pump, not your home's water pressure. Your Cala pauses heating until the reading returns. Restart your Cala once. If the code stays or comes back, contact your installer or [email protected]. With power off at the breaker, check the pressure sensor connectors and cables. Never open the sealed refrigerant circuit. Contact Cala support.

S_11_3
Safety CPU is Active

Your Cala has a second, independent safety system that watches the tank temperature and the heat pump. It has stopped all heating. It releases by itself once the cause is gone. Contact [email protected] and tell us any other code on the screen. Don't keep switching the power off and on to clear it. If you smell burning or see scorching or water at the unit, turn off its circuit breaker. Contact Cala support before doing any work. Never bypass or defeat the safety system.

S_12_0
Flowmeter is Over Range

S_12_2
Flowmeter is Nan

The sensor that measures how much hot water you use is giving a reading that can't be right. Your Cala pauses heating until the reading returns. Restart your Cala once. If the code stays or comes back, contact your installer or [email protected]. With power off at the breaker, check the flow meter's cable and connector.

S_26_0, S_26_1, S_26_2
System Voltage is Over Range / Under Range / NaN

The supply voltage your Cala measures is far too high, far too low or unreadable. Your Cala pauses heating until the reading returns. This can happen briefly around a power outage. If lights dim or flicker in your home, call your electric utility or an electrician. If the code stays, contact your installer or [email protected]. Measure the supply voltage at the unit's terminal block and check the supply wiring connections.

S_27_0, S_27_1, S_27_2
System Idle Current is Over Range / Under Range / NaN

During its start-up checks, your Cala measured an electrical current that doesn't make sense with everything switched off. If the code stays or comes back, contact your installer or [email protected]. Check for a relay that is stuck closed and check the current sensor. Contact Cala support.

Heating element codes (E)

Your Cala has two electric heating elements, upper and lower, that back up the heat pump. Codes with 15 are for the upper element and codes with 16 are for the lower.

Code and message What it means What to do For your Cala Pro

E_15_9
Upper Element Restart Frequency Too High

E_16_9
Lower Element Restart Frequency Too High

A heating element was switched on 10 times within 5 minutes. Your Cala pauses heating for 5 minutes, then carries on by itself. Nothing to do. If you see it often, contact your installer or [email protected]. Contact Cala support if it repeats.

E_15_5
Upper Element Over Current Detected

E_16_5
Lower Element Over Current Detected

A heating element is drawing more electrical current than it should. Your Cala pauses heating, waits and tries again. Contact your installer or [email protected]. With power off at the breaker, measure the element's resistance and inspect its wiring. Check the supply voltage. Replace the element if it is out of spec, then select CLEAR LOCKOUTS.

E_15_12
Upper Element Under Current Detected

E_16_12
Lower Element Under Current Detected

A heating element is drawing less electrical current than it should, which usually means the element or its wiring has failed. Your Cala pauses heating, waits and tries again. Contact your installer or [email protected]. With power off at the breaker, measure the element's resistance and check its wiring and connections. Check the supply voltage on both legs. Replace the element if it is open, then select CLEAR LOCKOUTS.

Leak codes (L)

Leak codes come with the leak alarm. The code and the alarm clear by themselves as soon as the sensors are dry. For the full steps, see Leak and heat pump alarms.

Code and message What it means What to do For your Cala Pro

L_23_16
Condensate Tray Full

The drip tray under the heat pump is full of water. The heat pump stays off until the tray is dry, and the heating elements keep your water hot. Follow the steps in Leak and heat pump alarms, then check the condensate line. Clear a condensate drain line that is clogged, kinked or frozen, and check the condensate pump if one is fitted. Re-route the line if it can't drain.

L_24_16
Floor Leak Detected

The leak detector on the floor under your Cala is wet. This is an alert only: your Cala keeps heating and does not shut off the water. Follow the steps in Leak and heat pump alarms to turn off the power and water and find the source. Check the plumbing fittings, the temperature and pressure relief valve discharge, and the condensate drain. Contact Cala support if the water is coming from the unit itself.

L_25_16
Combined Leak Detected

Both the floor leak detector and the drip tray are wet. The heat pump stays off until the tray is dry, and the heating elements keep your water hot. Follow the steps in Leak and heat pump alarms straight away. Check everything listed for the two codes above. Contact Cala support if the water is coming from the unit itself or the codes return with a clear drain.

Wi-Fi codes (C)

Wi-Fi codes don't appear on the Home screen. The Wi-Fi icon there shows Not Connected instead.

Code and message What it means What to do For your Cala Pro

C_21_15
WiFi Disconnected

Your Cala has been offline for more than a minute. It keeps heating normally. The Cala app, energy-saving features that need the internet and software updates wait until it is back online. Reconnect your Cala to Wi-Fi. Check the Wi-Fi signal where the unit is installed and that the router's 2.4 GHz band is on.

C_22_15
Sidewalk Disconnected

Not used by current Cala software. You should not see this code. If you do, contact [email protected]. Contact Cala support.

Software update codes (O)

Software update codes never affect your hot water and don't appear on the Home screen. If an update can't finish, your Cala keeps running the version it has and tries again later. Each code clears by itself after 30 minutes. See Firmware updates.

Code and message What it means What to do For your Cala Pro

O_17_17
HTTP Connect S3 Endpoint Failure

O_26_31
Ota Process failed to start

O_20_30
App update download is incomplete

Your Cala couldn't reach the update service, or the download was interrupted. Check that your Cala is online. If its Wi-Fi drops often, reconnect it to Wi-Fi. Your Cala tries the update again by itself. Check the Wi-Fi signal where the unit is installed.

O_17_18
Ota URL Decode Failure

O_20_29
Failed to load app description details

O_26_27
Ota Process unexpectedly failed

The update file couldn't be read or didn't finish installing. Nothing to do. Your Cala tries the update again by itself. Nothing to service.

O_18_19
No Public Key found

O_18_20
Failed to update public key

O_18_21
Failed to load public key

O_18_22
Failed to decode update signature

O_18_23
Failed to verify update signature

Your Cala checks that every update really comes from Cala before installing it. This update didn't pass that check, so it was not installed. Nothing to do. If your Cala stays on an old version, contact [email protected]. Nothing to service. Contact Cala support if it repeats.

O_19_24
Failed to cancel rollback

O_19_25
App version already rolled back. Update Unstable

O_19_26
Failed to get the rollback state

O_19_27
App update is in an unexpected state

O_19_32
Repeated crashes, rolled back automatically

A new version didn't run properly after it installed, so your Cala went back to the version it was running before. Nothing to do. Your Cala keeps working on its earlier version and gets the next update by itself. Nothing to service.

O_20_28
Update is not a version upgrade

The update on offer isn't newer than the version your Cala already has. Nothing to do. Nothing to service.

Clock codes (G)

Your Cala has a built-in clock with a backup battery. Clock codes never affect your hot water and don't appear on the Home screen. They are checked when your Cala starts and clear by themselves after 30 minutes.

Code and message What it means What to do For your Cala Pro

G_27_33
RTC lost power including battery backup

The built-in clock lost its time while your Cala was without power. Your Cala sets its clock again from the internet. Keep your Cala connected to Wi-Fi. Nothing else to do. Contact Cala support if it appears after every power loss.

G_27_34
RTC oscillator fault

G_27_35
RTC I2C failure

The built-in clock isn't working properly. Your Cala sets its clock from the internet instead. Keep your Cala connected to Wi-Fi. If the times on your Cala look wrong, contact [email protected]. Contact Cala support.

Clear a lockout

If the same problem happens many times in a row, your Cala stops retrying (a lockout). Once the cause is fixed, select CLEAR LOCKOUTS on the ADVANCED screen. See Restart or factory reset your water heater for the steps.